Support
QA12 Conventional Fire Alarm Control Panel
- QA12
Hiện tại chưa có tài liệu để download
Characteristics
- QA12 up to 80 zones.
- Each zone has a separate disable function.
- Zone test mode to perform alarm and fault functional test.
- Alarm verification up to 7 seconds for real fire confirmation and avoid false alarm from environment interference.
- Fault indicatio
Specification
QA12 Conventional Fire Alarm Control Panel
Model QA12 Power 220V AC, 50/60Hz *Others also available Battery Capacity 24V/4Ah # of heat detectors connected No limit *Except electronic type # of smoke detectors connected 30/zone *Horing Lih manufactured End of Line Resistor 10kΩ *One per zone Material 1.2mm steel plate Color Pearl gray Cabinet Dimensions
Model / Zone Dimensions (mm) H x W x D QA12 10 zone 450 x 330 x 130 QA12 20 zone 550 x 330 x 130 QA12 30 zone 680 x 380 x 150 QA12 40~50 zone 950 x 420 x 150 QA12 60~80 zone 1300 x 420 x 170 Optional Device
Optional Relay Output per 10 zone Optional Telephone Handset 2 pcs