Characteristics

  • EN54-5 Approval.
  • The standard detector is 2-wire or 3-wire with base.
  • For 4-wire type just add one relay output module on 3-wire base. Simple and easy module placement enables wider application.
  • Dual LEDs for 360-degree visibility. Bi-color LED, Stand-by Status: Green; Alarm Status: Red.
  • Detector is made of high endurance, solid and colorfast Fire-proof plastic.
  • Non-loosening screws on base terminal for easy installation.
  • Detector has passed strict EMC test, which greatly eliminates false alarms caused by interference from nearby sources. 

Specification

Q06 Conventional Heat Detector 

ModelQ06-2Q06-3Q06-4
Alarm ContactN/A  N/A0.8A @30V DC, 0.4A @125V AC
Voltage Range12 ~ 30V DC
Alarm Current@24V DC 470Ω40mA40mA45mA
Standby Current@24V DC 470Ωunder 95μA
Thermal Setting 58℃
Ambient Temperature-10℃ ~ +55℃
MaterialFire-proof plastic
Dimensions102mm(Dia.) x 46mm(H)
Weight 115g115g130g
ColorWhite

Effective Alert Area

Construction/HeightUnder 4M4M ~ 8M
Fire-proof Building90 M245 M2
Ordinary Building50 M230 M2