AH-0625 UL Smoke and Heat Detector

  • AH-0625

Hiện tại chưa có tài liệu để download

Characteristics

  • UL Listed.
  • Dual LEDs for 360-degree visibility.
  • Each visible warning has 3 modes to easily identify current status. 
  • Microprocessor control makes smoke and heat detection more accuracy.
  • The standard detector is 2-wire or 3-wire with base.
  • For 4-wire type just add one relay output module on 3-wire base. Simple and easy module placement enables wider application.
  • Detector is made of high endurance, solid and colorfast Fire-proof plastic.
  • Non-loosening screws on base terminal for easy installation.
  • Detector has passed strict EMC test, which greatly eliminates false alarms caused by interference from nearby sources.

Specification

AH-0625 UL Listed Combination Smoke and Heat Detector

ModelAH-0625-2AH-0625-3AH-0625-4
Alarm ContactN/A  N/A0.8A @30V DC, 0.4A @125V AC
Voltage Range12 ~ 30V DC
Alarm Current @24V DC 470Ω40mA40mA45mA
Standby Current @24V DC 470Ω30 ~ 80μA
Sensitivity SettingComply to UL 268 
Thermal Setting57℃
IndicatorStandby: flash every 4 sec. / Pre-alarm: flash every 2 sec. / Abnormal: flash once every sec.
Ambient Temperature0℃ ~ +37.8℃
MaterialFire-proof plastic
Dimensions102mm(Dia.) x 54mm(H)
Weight 130g 130g 145g
ColorWhite

Effective Alert Area

 

Building HeightArea Covered
Under 4M150 M2
4 ~ 20M75 M2

Order Information

AH-0625-22-wire 
AH-0625-33-wire with remote indicator output
AH-0625-44-wire with relay output 

Bình luận